Generator Maintenance
Generac 20-Point Inspection
Keeping YOUR Power On
Upon Arrival:
- Visual check, look for oil leaks, check battery year
- Check oil level
- Check battery terminals for corrosion and tight connections
– Try manual start - Listen to the harmonics (cranking power, duration of crank, running, listen for any loud ‘clicking’ on metal noise (valves))
60Hz +/- 4 Hz (depending on year and model)
240VAC (210-215 for capacitor models)
3600RPM +/- 75 RPM - Listen for exhaust flex hose (under HOT panel), any cracks/loudness
-Shut generator down and listen for any metal on metal clanking - Change oil and oil filter (write the date and run hours on filter)
- Check air filter, replace every 3 years or 200 run hours or as needed
- Check spark plugs, replace every 3 years or 100 run hours or as needed
- Check and adjust valves every 200 run hours
- Check stepper motor or mechanical linkage (depending on year)
- Check starter connections and starter contactor connections (depending on year)
- Check choke solenoid (depending on year)
- Check hoses and hose clamps
- Check fuel line
- Reset maintenance button
- Correct time of day
- Update firmware
- Ohm brush assembly wire 4 and 0 if generator is 10 years or 400 run hours
- Clean dust, dirt, grass, oil, bugs, leaves, snow inside/outside and around intake vents
- Apply Rustoleum spray paint in appropriate locations